model |
DR-45-5 |
DR-45-12 |
DR-45-15 |
HDR-45-24 |
output |
Dc output voltage |
5V |
12V |
15V |
24V |
Output voltage tolerance |
±2% |
±1% |
±1% |
±1% |
Rated output current |
5A |
3.5A |
2.8A |
2A |
Output current range |
0-5A |
0-3.5A |
0-2.8A |
0-2A |
Output power |
25W |
42W |
42W |
48W |
Ripple and the noise |
100mVp-p |
200mVp-p |
240mVp-p |
480mVp-p |
Dc voltage adjustable scope |
4.75-5.5V |
10.8-13.2V |
13.5-16.5V |
21.6-26.4V |
Start, rise, keep time |
800ms,60ms,100ms/230VAC Loaded with |
input |
Input voltage range |
85~264 VAC47~63 Hz;choose 120~370VDC |
Exchange input current |
1.5 A/115 V 0.75A/ 230 V |
efficiency |
72% |
77% |
77% |
80% |
Impulse current |
Cold start current 28A/115V 56A/230V |
Leakage current |
<1mA/240VAC |
Protection characteristics |
Overload protection |
105%~150% |
Protection way: constant current limiting automatic recovery |
Overvoltage protection |
115%~135% |
Protection way: cut output, restart |
High temperature protection |
Power tube to 135 ℃, the temperature drop, cut off output automatically after recovery |
environment |
Working temperature, humidity |
-10℃~+50℃;20%~90 %RH |
Keep temperature, humidity |
-20℃~+85℃;10%~95 %RH |
Vibrate resistance |
10~500Hz,2G 10min./1 cycle time, 60 minutes, the axis |
security |
Compression sex |
3: KVAC between input and output and input and output KVAC: 1.5 to 0.5: KVAC |
Insulation resistance |
Between the input and output, the input and output, and ground: 100M Ohms / 500VDC |
Complies with the standards |
Safety standards |
Accord with UL508,TUV EN60950-1 |
EMC standard |
Accord with EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2 |
other |
weight |
0.31Kg |
packaging |
48pcs/16.1Kg/1.3CUFT |
备注 |
1. All the parameters in has not specified, all is in 230 VAC voltage input, rated load and 25 ℃ conditions measuring income value. |
2. Ripple and noise voltage is in 20 MHz bandwidth oscilloscope take 12 inches twisted pair end with 0.1 mu and 47 u when capacitance measurement. |
3. Tolerance is voltage setting error, the voltage adjustment rate and adjust the sum total of the current rate. |
4. The power to consider as a device installed in final equipment, this equipment must be to make sure it’s EMC index. |