Features:
vice rated voltage mode power supply
Had 170 ~ 264 VAC input range
Had small volume, light weight, high efficiency
Characteristics: short circuit protection miscalculates/overload/pressure/thermal
Had air cooling
Meet the IP67 miscalculates level
Had 100% full load test machine and
Had 2 years quality assurance
Size: 182 x had 30 x 20 mm
Technical parameter:
model |
LPV-20-12 |
LPV-20-24 |
LPV-20-36 |
output |
Dc output voltage |
12V |
24V |
36V |
Output voltage tolerance |
±1% |
±1% |
±1% |
Rated output current |
1.7A |
0.8A |
0.6A |
Output current range |
0~1.7A |
0~0.8A |
0~0.6A |
Output power |
20W |
20W |
21W |
Ripple and the noise |
100mVp-p |
100mVp-p |
150mVp-p |
Dc voltage adjustable scope |
±10% |
±10% |
±10% |
Start, rise, keep time |
800ms,20ms,24ms/230VAC |
input |
Input voltage range |
170~264VAC 47~63Hz,235~373VDC |
Exchange input current |
0.28A/230VAC |
efficiency |
76% |
78% |
80% |
Impulse current |
Cold start current 30A/230VAC |
Leakage current |
<0.5mA/240VAC |
Protection characteristics |
Overload protection |
Protection way: hiccups mode, load abnormal conditions can be removed recovery |
environment |
Working temperature, humidity |
-10℃~+60℃;20%~90%RH(Please refer to reduce the specified number load curve ) |
Keep temperature, humidity |
-20℃~+85℃;10%~95%RH No condensation |
Vibrate resistance |
10~500Hz,2G 10min./1 cycle time, 60 minutes, the axis |
security |
Compression sex |
Between input and output :1.5KVAC |
Insulation resistance |
Between input and output :100M Ohms/500VDC |
Complies with the standards |
Safety standards |
Accord with UL1012 |
EMC standard |
Accord with EN55022,CLASSA |
other |
weight |
0.22kg 182*30*20(L*W*H) |
packaging |
0.22kg/80pcs/18.5kg |
note |
1. All the parameters in has not specified, all is in 230 VAC voltage input, rated load and 25 ℃ conditions measuring income value. |
2. Ripple and noise voltage is in 20 MHz bandwidth oscilloscope take 12 inches twisted pair end with 0.1 mu and 47 u when capacitance measurement. |
3. Tolerance is voltage setting error, the voltage adjustment rate and adjust the sum total of the current rate. |
Installation dimensions:
|