Main characteristics

○Small volume, convenient for installing and maintenance, good water proof performance, and can be used for both outdoor and indoor.

○Controlling parameter full digital operation, convenient for using, the date can not lose when power off.

○Digital display power network power factor, reactive power, voltage, current(one side), contro parameter

○With the function of over-voltage, under-voltage judgment displays and fast cut off the compensated capacitor group.

○With two working modes of manual and auto compensation.

○it has the function of auto selecting the best mode to input and cutoff compens ation according to the result of capacitor group manual input.

○With two working modes of cycle or optimizing input and cutoff the compensation includes controlling mode of 1:1:1:1,1:2:2:2,1:2:4:8,the compensator will automatically distinguish its code working mode of manual input duplexure capacitance value ,it works according to the correspondence code mode.

○With two working modes of power factor or reactive power.

○Compensating mode: ①phase splitting compensation②phase splitting and three-phase compensation ③three –phase compensation

○control mode: ①crystal braking-tube input and cutoff ②compound switch input and cutoff

Main technical characteristics

○service conditions :Altitude:≤2000m

Ambient temperature:-25℃~50℃,

Humidity:≤90%at 20℃;≤90%at 40℃,

Installing gradient:≤5°

○Usage voltage range(0.85~1.10)times rated voltage

○Max .Allowable over-current:1.3 times rated current

○Control loop no:1~12(settable)

○input and cutofftime: dynamic state 100ms~30S,

Static state 1~250s(settable)

○Under-voltage protection:340V/180V;

Return difference 6V

○over-voltage protection:380-500/230-260V

Return difference 6V (settsble)

○CT variation:50/5A-3000/5A(settable)

○Sensitvity:100mA

○Measurement precision:

Voltage:±1.0%

Current: ±1.0%

Power factor: ±1.0%

Reactive power: ±2.0%

 